transformer and electric-power transmission

Learning objectives

  • Outcome

    Calculate the secondary voltage and current of an ideal transformer from given turns numbers and primary-circuit data using U2U1=N2N1\frac{U_2}{U_1}=\frac{N_2}{N_1} and U1I1=U2I2U_1I_1=U_2I_2.

  • Outcome

    Determine the power loss in a transmission line with Ploss=I2RP_{loss}=I^2R and express it as a percentage of the transmitted power.

  • Outcome

    Explain why raising the transmission voltage reduces losses, and demonstrate this with a numerical comparison of two transmission options.

  • Outcome

    Draw a transmission-chain diagram (step-up transformer, line, step-down transformer, consumer) and label voltages, currents and turns numbers on it.

Understand the idea

Transformer and Electric Power Transmission

Text

A transformer works because of electromagnetic induction: the alternating current in the primary coil produces an alternating magnetic flux in the core, and this flux induces an emf in the secondary coil. Both coils are threaded by practically the same flux, so the emfs are proportional to the numbers of turns:

U2U1=N2N1.\frac{U_2}{U_1}=\frac{N_2}{N_1}.

For an ideal transformer the power is conserved:

U1I1=U2I2,U_1I_1=U_2I_2,

so raising the voltage by a factor kk lowers the current by the same factor. When energy travels along a line of resistance RR, the loss is Ploss=I2RP_{loss}=I^2R, so a smaller current sharply reduces the loss. That is why the voltage is stepped up before the line and stepped down before the consumer. A transformer cannot work on direct current: without a changing magnetic flux there is no emf in the secondary coil.

Worked examples

Direct

Problem

An ideal transformer is connected to a U1=240U_1 = 240 V supply. The primary coil has N1=1000N_1 = 1000 turns and the secondary coil has N2=50N_2 = 50 turns. Find the secondary voltage U2U_2 and state the type of the transformer.

Solution

Use the turns-ratio relation:

U2=U1N2N1=240⋅501000=12 V.U_2 = U_1\frac{N_2}{N_1} = 240 \cdot \frac{50}{1000} = 12 \text{ V}.

Since N2<N1N_2 < N_1, this is a step-down transformer. From power conservation U1I1=U2I2U_1I_1=U_2I_2, the secondary current is 240/12=20240/12 = 20 times larger than the primary current.

Application

Problem

A power station delivers P=10P = 10 MW through a transmission line of resistance R=2R = 2 Ω. Compare the power lost in the line when the transmission voltage is (a) UA=10U_A = 10 kV and (b) UB=400U_B = 400 kV. Express each loss as a percentage of PP.

Solution

The line current follows from P=UIP = UI and the loss from Ploss=I2RP_{loss}=I^2R.

(a) IA=107104=1000I_A = \frac{10^7}{10^4} = 1000 A, hence

Ploss,A=IA2R=106⋅2=2⋅106 W=2 MW,P_{loss,A} = I_A^2 R = 10^6 \cdot 2 = 2 \cdot 10^6 \text{ W} = 2 \text{ MW},

that is 2/10=0,20=20%2/10 = 0{,}20 = 20\% of the transmitted power.

(b) IB=1074⋅105=25I_B = \frac{10^7}{4 \cdot 10^5} = 25 A, hence

Ploss,B=252⋅2=1250 W,P_{loss,B} = 25^2 \cdot 2 = 1250 \text{ W},

which is 1250107=1,25⋅10−4=0,0125%\frac{1250}{10^7} = 1{,}25 \cdot 10^{-4} = 0{,}0125\%.

The voltage rose 40 times, the current fell 40 times, and the loss fell 402=160040^2 = 1600 times.

Transfer

Problem

A generator produces P=100P = 100 kW at 2 kV. A village is connected to it by a line of resistance R=5R = 5 Ω.

  • Option A: transmit directly at 2 kV.
  • Option B: step up to 40 kV with an ideal transformer, transmit, then step down with an ideal transformer of turns ratio 100:1100:1.

For each option find the line loss and the voltage arriving at the village. Which option should be chosen?

Solution

Option A. I=PU=1052000=50I = \frac{P}{U} = \frac{10^5}{2000} = 50 A.

Ploss=I2R=502⋅5=12 500 W=12,5 kW  (12,5%).P_{loss} = I^2R = 50^2 \cdot 5 = 12\,500 \text{ W} = 12{,}5 \text{ kW} \;(12{,}5\%).

The line voltage drop is ΔU=IR=50⋅5=250\Delta U = IR = 50 \cdot 5 = 250 V, so the village receives 2000−250=17502000 - 250 = 1750 V.

Option B. After the step-up transformer, I=10540 000=2,5I = \frac{10^5}{40\,000} = 2{,}5 A.

Ploss=2,52⋅5=31,25 W  (≈0,03%).P_{loss} = 2{,}5^2 \cdot 5 = 31{,}25 \text{ W} \;(\approx 0{,}03\%).

The drop is ΔU=2,5⋅5=12,5\Delta U = 2{,}5 \cdot 5 = 12{,}5 V, so the input of the step-down transformer is 40 000−12,5=39 987,540\,000 - 12{,}5 = 39\,987{,}5 V. With a 100:1100:1 ratio the village receives

Uvillage=39 987,5100≈400 V.U_{village} = \frac{39\,987{,}5}{100} \approx 400 \text{ V}.

Conclusion: choose option B. Nearly all the power reaches the consumer, and the line loss dropped by a factor of about 400 because the current fell 20 times.

Practice

Text

Self-check in a simulation (safe, no mains).

  1. Open an interactive AC-circuit model with an ideal transformer (adjustable N1N_1, N2N_2 and a resistive load). Do not connect real transformers to the mains: 220 V work is hazardous.
  2. Set U1=100U_1 = 100 V and N1=1000N_1 = 1000 turns. Vary N2N_2 from 100 to 2000 in steps of 100, recording U2U_2 and I2I_2 with an unchanged load resistance.
  3. Plot U2U_2 against N2N_2 and check U1I1≈U2I2U_1I_1 \approx U_2I_2 at every point. Mark where the transformer steps up and where it steps down.
  4. In a spreadsheet set P=1P = 1 MW, R=4R = 4 Ω and compute Ploss%=(P/U)2RP⋅100%P_{loss}\% = \frac{(P/U)^2 R}{P} \cdot 100\% for UU from 1 kV to 100 kV. Plot the loss fraction against the transmission voltage (logarithmic UU axis) and state the conclusion in one sentence.

Visual reference

Purpose

Show the whole power-transmission chain and the quantitative link between the transmission voltage and the line loss.

Representation

A two-part diagram. On the left, the circuit: generator →\rightarrow step-up transformer (N1:N2N_1:N_2) →\rightarrow line of resistance RR →\rightarrow step-down transformer →\rightarrow consumer; each element is labelled with UU and II, and arrows show the direction of power flow. On the right, a small graph: the horizontal axis is the transmission voltage UU (logarithmic scale), the vertical axis is the loss fraction I2R/PI^2R/P in percent; the curve falls monotonically, with marked points for 10 kV and 400 kV.

Real-world examples

High-voltage transmission from a power station

Scenario

A power station sends P=1000P = 1000 MW to a city 200200 km away. The transmission line has a total resistance R=10 ΩR = 10\ \Omega. A step-up transformer raises the generator voltage from 2020 kV to 400400 kV before the line. At 400400 kV the line current is I=P/V=2500I = P/V = 2500 A, so the heating loss in the line is Ploss=I2R=62.5P_{\text{loss}} = I^2 R = 62.5 MW, about 6.3%6.3\% of the transmitted power. If the same power were sent at 2020 kV, the current would be 50 00050\,000 A and the loss would be 25 00025\,000 MW, which no practical line can carry. Near the city, substations step the voltage down to 1010 kV and then to 400400 V for homes.

Connection

This uses the ideal-transformer relations V1/V2=N1/N2V_1/V_2 = N_1/N_2 and P1=P2P_1 = P_2, together with the current ratio I1/I2=N2/N1I_1/I_2 = N_2/N_1. It also exercises the reason for high-voltage transmission: for fixed power, I=P/VI = P/V, so raising VV lowers II and the resistive loss I2RI^2 R falls as 1/V21/V^2.

Phone charger

Scenario

A phone charger is plugged into a 230230 V socket and delivers 55 V at 22 A to the phone, so the output power is 1010 W. Inside the charger there is a small transformer with a turns ratio of about 46:146:1, followed by a rectifier that changes the alternating current to direct current. The current drawn from the socket is about 10/230≈0.04310/230 \approx 0.043 A.

Connection

This applies the step-down transformer equation V2=V1N2/N1V_2 = V_1 N_2/N_1: to get 55 V from 230230 V the secondary must have about 1/461/46 as many turns as the primary. It also shows power conservation P1=P2P_1 = P_2 in the ideal transformer: the small primary current 0.0430.043 A at 230230 V supplies the same 1010 W as 22 A at 55 V.

Electric locomotive transformer

Scenario

An electric locomotive collects power from a 2525 kV overhead line and uses an on-board transformer to step the voltage down to 1.51.5 kV for its traction motors. For a motor input power of 55 MW, the secondary current is I=P/V=5 000 000/1500≈3333I = P/V = 5\,000\,000/1500 \approx 3333 A, while the primary current is only 5 000 000/25 000=2005\,000\,000/25\,000 = 200 A. The overhead wire therefore carries a much smaller current and wastes less energy in its resistance.

Connection

This exercises the same step-down transformer relations as the charger, now at high power: V1/V2=N1/N2V_1/V_2 = N_1/N_2 and I1/I2=N2/N1I_1/I_2 = N_2/N_1. It shows why transport systems use high voltage on the catenary: for the same power, lower current in the long overhead wire means lower I2RI^2 R loss.